      Differential pressure transmitter Single crystal silicon pressure transmitter Electromagnetic flowmeter Capacitive pressure transmitter High precision pressure transmitter Intelligent pressure switch Diffused silicon pressure transmitter Flow switch Intelligent pressure transfer controller Thermometer

      Pressure transmitter


      BXY6001 Differential Pressure

      Product code

       

      Overview

      Product quotationProduct consulting

      Product introduction


      BXY6001 Differential Pressure Remote Transmission Transmitter
      1 Application
      The diaphragm box of the differential pressure remote transmitter is used to prevent the medium in the pipeline from directly entering the pressure sensor component of the differential pressure transmitter. It uses silicone oil and other filling liquids to transmit pressure between the transmitter and it.
      The BXY6001 differential pressure remote transmitter is used to measure the liquid level, density, pressure, and flow rate of liquids, gases, or vapors, and then convert it into a 4-20mADC HART current signal output. BXY6001 can also communicate with RST375 handheld terminals or RSM100 Modems for parameter setting, process monitoring, etc. The measurement range of BXY6001 differential pressure remote transmitter (when not relocated) is 0-1kPa~2MPa, and the rated pressure of the remote flange is 1.6/4MPa, 6.4MPa, 10MPa, 150psi, 300psi, or 600psi, respectively.
      2 Working principle
      The BXY6001 differential pressure remote transmission transmitter consists of a BXY6001 series differential pressure transmitter and a welded and installed capillary remote transmission flange. Its working principle is the same as the BXY6001 series differential pressure transmitter (refer to the technical specifications of the BXY6001 series differential pressure transmitter), but the pressure transmission path is slightly different: the pressure acting on the remote flange side first passes through the diaphragm and filling liquid on the remote flange, then through the capillary, and finally reaches the corresponding positive and negative sides of the measurement sensor.
      3 inputs
      Measurement parameters: differential pressure, liquid level
      Measurement range
      Lower limit value: from -100% URL (continuously adjustable)
      Upper limit value: to+100% URL (continuously adjustable)
      Range
      Table 1 Comparison Table of Range Code and Range Range Relationship


      Range code

      minimum range

      maximum range

      Rated pressure (maximum)

      B

      1kPa

      6kPa

      Rated pressure of remote transmission flange

      C

      4kPa

      40kPa

      D

      25kPa

      250kPa

      E

      200kPa

      2MPa

      Table 2 Comparison Table of the Relationship between Remote Transmission Flange and Minimum Range

      Level flange

      Nominal diameter

      minimum range

      Unilateral remote transmission

      Bilateral remote transmission

      Flat type

      DN 50/2”

      10kPa

      10kPa

      DN 80/3”

      6kPa

      1kPa

      DN 4”

      6kPa

      1kPa

      plug-in

      DN 50/2”

      16kPa

      16kPa

      DN 80/2”

      6kPa

      1kPa

      DN 4”

      6kPa

      1kPa

      The minimum range of the remote transmitter should be the larger value of the minimum range in Table 1 and Table 2. The adjusted range shall not be less than the minimum range. The maximum range of the remote transmitter should be the minimum of the maximum range of the transmitter body and the rated pressure of the liquid level flange.
      4 outputs
      output signal
      2-wire system, 4-20mADC HART output, digital communication, with HART protocol loaded on 4-20mADC signal.
      Output signal limit: Imin=3.9mA, Imax=20.mA
      Alarm current (mode can be set)
      Low alarm mode (minimum): 3.7 mA
      High alarm mode (maximum): 21 mA
      No alarm mode (hold): maintain the effective current value before the fault
      Alarm current standard setting: high alarm mode
      5 Response time
      The damping constant of the amplifier component is 0.1s; The time constant of the sensor and remote flange is 0.2-6s, depending on the sensor's range, range ratio, capillary length, and viscosity of the filling liquid. The additional adjustable time constant is 0.1~60s.
      6 General conditions
      6.1 Installation conditions
      The transmitter body can be directly fixed in any position. The optimal state is to keep the process flange axis in a vertical position, and the positional deviation will result in a correctable zero offset. The electronic watch case can rotate up to 360 °, and the positioning screw can fix it in any position.
      The remote flange is connected to a matching flange that complies with ANSI/DIN standards. The matching flange should be equipped with soft gaskets and fixed bolts and nuts (users can choose to install bolts and nuts).
      For bilateral flange remote transmitters, capillary components and remote flanges should only be installed in the same ambient temperature. The minimum bending radius of the capillary is 75mm, and winding is strictly prohibited!
      6.2 Environmental conditions
      ambient temperature
      Minimum: depending on the filling fluid
      Maximum: 85 ℃
      When equipped with LCD display and fluororubber sealing ring, -20~65 ℃
      Storage temperature/transportation temperature
      Minimum: depending on the filling fluid
      Maximum: 85 ℃
      Relative humidity: 0-100%
      Impact resistance
      Acceleration: 50g
      Duration: 11ms
      Anti vibration
      2g to 500Hz
      Electromagnetic compatibility (EMC)
      See Table 4 "Electromagnetic Compatibility Schedule" on the next page
      6.3 Process Medium Limits
      Temperature limit
      Medium temperature: -30~400 ℃
      Table 3 Relationship between Filling Fluid, Working Temperature, and Minimum Working Static Pressure


      Fill Fluid

      silicone oil

      (S)

      High temperature

      silicone oil(H)

      Ultra high temperature

      silicone oil(U)

      vegetable oil(V)

      density25℃

      960

      kg/m3

      980

      kg/m3

      1020

      kg/m3

      937

      kg/m3

      Working temperature
      Degree range


      -30~

      200℃

      -10~

      350℃

      -10~

      400℃

      0~

      250℃


      temperature

      Working static pressure range (kPa absolute pressure)

      20℃

      >10

      >10

      >10

      >25

      100℃

      >25

      >25

      >25

      >50

      150℃

      >50

      >50

      >50

      >75

      200℃

      >75

      >75

      >75

      >100

      250℃


      >100

      >100

      >100

      350℃


      >100

      >100


      400℃



      >100


      Note: Those exceeding the range of working temperature and static pressure relationship above should be specifically pointed out, and special designs can be used to meet the requirements.
      Transmitter body pressure limit
      From an absolute pressure of 3.5kPa to the rated pressure, the protective pressure can be greater than 1.5 times the rated pressure and applied to both sides of the transmitter.
      Rated pressure of remote transmission flange
      ANSI standard: 150psi~600psi
      DIN standard: PN 1.6MPa~PN 10MPa
      Unidirectional overload limit
      The low pressure side is the rated pressure of the transmitter body, while the high pressure side is the rated pressure of the remote flange, which may cause adjustable zero drift.
      Weight
      Unilateral remote transmission is about 7-10kg for DN 50/2 ", 8-11kg for DN 80/3", and 9-12kg for DN 4 ";
      Bilateral remote transmission is about 10-16.5kg for DN 50/2 ", 12-18kg for DN 80/3", and 14-21kg for DN 4 ".
      Explosion proof performance
      NEPSI Flameproof License: Ex d Ⅱ C T6
      NEPSI Intrinsic Safety License: Ex ia IIC T4
      Permissible operating temperature: -40 ℃~65 ℃
      6.4 Power supply and load conditions
      The power supply voltage is 24V
      R ≤ (Us-12V)/Imax k Ω
      Where Imax=23 mA
      Maximum power supply voltage: 42VDC
      Minimum power supply voltage: 12VDC, 15VDC (backlight LCD display)
      Digital communication load range: 250~600 Ω
      material quality
      Measurement capsule: stainless steel 316L
      Diaphragm: stainless steel 316L, Hastelloy C, tantalum
      Process flange: stainless steel 304
      Filling fluid: silicone oil, high-temperature silicone oil, ultra-high temperature silicone oil, vegetable oil
      Sealing ring: nitrile rubber (NBR), fluororubber (FKM)
      Polytetrafluoroethylene (PTFE)
      Transmitter housing: aluminum alloy material, with epoxy resin sprayed on the surface
      Shell sealing ring: nitrile rubber (NBR)
      Nameplate: stainless steel 304
      Electrical connections
      M20X1.5 cable sealing buckle and wiring terminal are suitable for wires ranging from 0.5 to 2.5mm2.
      Process Connection
      The low pressure side of the transmitter has NPT 1/4 and UNF 7/16 internal threads. The liquid level flange on the high-pressure side of the transmitter complies with ANSI or DIN standards. Can be installed directly, refer to Page 42 Part 7.
      Shell protection level: IP67
      Table 4 Electromagnetic Compatibility Schedule


      Serial Number

      Test items

      Basic standards

      Test conditions

      Performance Level

      1

      Radiated interference (shell)

      GB/T 9254-2008表5

      30MHz~1000MHz

      qualified

      2

      Conducted interference
      (DC power port)


      GB/T 9254-2008表1

      0.15MHz~30MHz

      qualified

      3

      Electrostatic discharge (ESD) immunity

      GB/T 17626.2-2006

      4kV(contact)

      8kV(air)

      B

      4

      Radio frequency electromagnetic

      field immunity

      GB/T 17626.3-2006

      10V/m (80MHz~1GHz)

      A

      5

      Power frequency magnetic

      field immunity

      GB/T 17626.8-2006

      30A/m

      A

      6

      Electrical fast transient pulse

      group immunity

      GB/T 17626.4-2008

      2kV(5/50ns,5kHz)

      B

      7

      Surge immunity

      GB/T 17626.5-2008

      1kV(Between lines)

      2kV(Between lines)

      (1.2us/50us)

      B

      8

      Immunity to conducted interference

      induced by radio frequency fields

      GB/T 17626.6-2008

      3V (150KHz~80MHz)

      A

      Note: (1) A performance level description: During testing, the performance is normal within the technical specification limits.
      (2) B performance level description: During testing, the function or performance is temporarily reduced or lost, but it can recover on its own, and the actual operating status, storage, and data remain unchanged.
      7 Dimensions in millimeters
      Figure 1 Basic bilateral differential pressure remote transmission sealing device diagram



      Figure 2 Basic Single Side Differential Pressure Remote Transmission Sealing Device Diagram

      Note: (1) The unilateral basic differential pressure remote sealing device can be installed on the high-pressure side of the transmitter body or on the low-pressure side of the transmitter;
      (2) The installation method of the transmitter body for single or double sided basic differential pressure remote transmission sealing devices is the same as that of the BXY6001 series differential pressure transmitter.
      Table 5 Structural Dimensions of Remote Transmission Flange





      ?